Automation Rules

Rules let you define threshold-based automations: when a sensor value meets a condition, WebMACS can log an alert or trigger a webhook delivery — without any code on your part.

Admin only

Rule management requires an admin account.


How Rules Work

flowchart LR
    DP[New Datapoint] --> EVAL{Rule matches?}
    EVAL -->|No| SKIP[Skip]
    EVAL -->|Yes| CD{Cooldown expired?}
    CD -->|No| SKIP
    CD -->|Yes| ACT[Fire action]
    ACT --> LOG[Log entry]
    ACT --> WH[Webhook delivery]

Every time a datapoint is created, WebMACS evaluates all enabled rules that target the same event:

  1. Condition check — compare the datapoint value against the rule's operator and threshold
  2. Cooldown check — skip if the rule fired recently (within cooldown_seconds)
  3. Action — log the alert and/or trigger a webhook delivery

Creating a Rule

Via the UI

  1. Navigate to Rules in the sidebar (admin only)
  2. Click New Rule
  3. Configure:
Field Required Description
Name Yes Descriptive label (e.g. "High Temp Alert — Reactor A")
Event Yes Which sensor event to monitor (dropdown)
Operator Yes Comparison operator (see table below)
Threshold Yes The value to compare against
Threshold High Only for between / not between Upper bound of the range
Action Type Yes log or webhook
Webhook Event Type Only for webhook actions Which webhook event type to dispatch
Cooldown (seconds) Yes Minimum seconds between consecutive triggers
Active Yes Enable or disable the rule
  1. Click Create

Via the API

curl -X POST http://localhost:8000/api/v1/rules \
  -H "Authorization: Bearer $TOKEN" \
  -H "Content-Type: application/json" \
  -d '{
    "name": "High Temp Alert",
    "event_public_id": "evt_temp_inlet",
    "operator": "gt",
    "threshold": 200,
    "action_type": "webhook",
    "webhook_event_type": "sensor.threshold_exceeded",
    "cooldown_seconds": 300,
    "enabled": true
  }'

Operators

Operator Symbol Condition Example
gt > Value is greater than threshold Temperature > 200
lt < Value is less than threshold Pressure < 0.5
gte Greater than or equal Flow ≥ 10
lte Less than or equal Level ≤ 5
eq = Equal (ε = 1e-9) Status = 1
between min ≤ x ≤ max Value is within range 20 ≤ Temp ≤ 80
not_between x < min or x > max Value is outside range Temp < 20 or > 80

Between vs Not Between

Use between to trigger when values are within a normal range — useful for confirming steady-state.
Use not_between to trigger when values go outside the safe range — this is the most common alerting pattern.


Action Types

Log

Creates a structured log entry when the condition is met. Visible on the Logs page. Useful for audit trails and post-experiment review.

Webhook

Dispatches a sensor.threshold_exceeded (or other) webhook event to all matching webhook subscriptions. Use this to send alerts to Slack, Teams, or custom APIs.

Combined setup

Create two rules for the same event:

  1. Inlet Temp > 200 → log (always log for audit)
  2. Inlet Temp > 250 → webhook (alert team only when critical)

Cooldown Period

The cooldown prevents rules from firing repeatedly when a sensor value stays above a threshold.

Cooldown Behaviour
60 s (default) At most one trigger per minute
300 s At most once every 5 minutes
0 s Fire on every matching datapoint (use with caution)

Alert fatigue

Setting cooldown to 0 with a webhook action can generate hundreds of deliveries per minute. Use a reasonable cooldown (60–300 s) for alerting.

gantt
    title Cooldown example (300 s)
    dateFormat X
    axisFormat %s
    section Rule fires
    Trigger 1           :done, 0, 1
    Cooldown (skip)     :active, 1, 300
    Trigger 2           :done, 300, 301
    Cooldown (skip)     :active, 301, 600

Rule Table Columns

Column Description
Name Rule label
Event Monitored sensor name
Operator Comparison symbol ( >, <, ≥, ≤, =, between, not between)
Threshold Threshold value (or range for between/not_between)
Action webhook or log badge
Active Enabled/disabled
Cooldown Seconds between triggers
Last Triggered Timestamp of last activation
Created Creation date

Example Scenarios

Event: Inlet Temperature
Operator: gt (>)
Threshold: 200
Action: webhooksensor.threshold_exceeded
Cooldown: 300 s

Sends a Slack notification when inlet temperature exceeds 200°C, at most once every 5 minutes.

Event: Chamber Pressure
Operator: not_between
Threshold: 0.8 / Threshold High: 1.2
Action: webhooksensor.threshold_exceeded
Cooldown: 60 s

Alerts when pressure goes below 0.8 bar or above 1.2 bar.

Event: Valve Status
Operator: eq (=)
Threshold: 1
Action: log
Cooldown: 0 s

Logs every time the valve opens (value = 1). Good for compliance trails.


Best Practices

Recommendations

  • Name rules descriptively — include the sensor name and threshold in the rule name
  • Set reasonable cooldowns — 60-300 s for webhook alerts, 0 s only for log-only actions
  • Combine log and webhook rules — log everything, webhook only critical thresholds
  • Use not_between for safe-range monitoring — it triggers when values leave the normal window
  • Review the Last Triggered column — rules that never fire may have incorrect thresholds

Next Steps

  • Webhooks — configure where webhook alerts are delivered
  • Events & Sensors — set up the sensors that rules monitor
  • Logs — view rule-triggered log entries